Daewoo DSA-095L Spécifications Page 38

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 98
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 37
37
Confirm following statement.
When the unit operate normally, Sometimes the outdoor unit and indoor unit cannot operate.
1 Is the setting temperature proper?
2 Is the unit during 3min. Time delay of compressor.
3 During frost prevention of lndoor unit.
4 During dehumidifier mode.
Outdoor Fan and Compressor Do Not
Check the voltge between and
of indoor unit terminal
Y
L
Check the voltge between and
of outdoor unit terminal
Y
L
Check the voltge between and
of outdoor unit terminal
Y
L
Check compressor,
outdoor fan motor individually
Check the
connecting wire
Check the
connecting wire
Check the wiring
and voltage
within doors
Rating voltage
under 90%
Rating voltage
under 90%
Rating voltage
under 90%
Vue de la page 37
1 2 ... 33 34 35 36 37 38 39 40 41 42 43 ... 97 98

Commentaires sur ces manuels

Pas de commentaire